Technical Document
Specifications
Brand
HOBUTSeries
CTRA
Overall Depth
70mm
Minimum Temperature
-30°C
Maximum Temperature
+85°C
For Use With
5A Moving Iron Meters
Country of Origin
United Kingdom
Product details
Toroidal Current Transformer
Power consumption 2.5VA
Accuracy class 1
For use with 5A moving iron meters or cam-operated selector switches
Full scale deflection depends on number of conductor turns through toroid as follows: 120A/0 (conductor passed straight through toroid); 60A/2; 40A/3; 30A/4; 20A/6; 15A/8; 10A/12
Secondary winding epoxy resin insulated
Suitable for 50/60Hz
BS7627/IEC185
Supplied with
integral mounting bracket, 83mm fixing centres
Current Transformers

AED 101.85
AED 101.85 Each (ex VAT)
AED 106.94
AED 106.94 Each (inc. VAT)
1
AED 101.85
AED 101.85 Each (ex VAT)
AED 106.94
AED 106.94 Each (inc. VAT)
1
Stock information temporarily unavailable.
Please check again later.
| Quantity | Unit price |
|---|---|
| 1 - 4 | AED 101.85 |
| 5 - 9 | AED 100.54 |
| 10+ | AED 100.06 |

Technical Document
Specifications
Brand
HOBUTSeries
CTRA
Overall Depth
70mm
Minimum Temperature
-30°C
Maximum Temperature
+85°C
For Use With
5A Moving Iron Meters
Country of Origin
United Kingdom
Product details
Toroidal Current Transformer
Power consumption 2.5VA
Accuracy class 1
For use with 5A moving iron meters or cam-operated selector switches
Full scale deflection depends on number of conductor turns through toroid as follows: 120A/0 (conductor passed straight through toroid); 60A/2; 40A/3; 30A/4; 20A/6; 15A/8; 10A/12
Secondary winding epoxy resin insulated
Suitable for 50/60Hz
BS7627/IEC185
Supplied with
integral mounting bracket, 83mm fixing centres
Current Transformers